Brunel Mk III Conventional FlueWith upgradeable control valveInstructions for Use,Installation and ServicingFor use in GB, IE (Great Britain and Eire)
102.3 Having run the gas supply to the stove, PURGE THE SUPPLY PIPE, this is essential to expel any debris that may block the gas controls. • Conn
11AR088642.7 • Placetheclosureplateagainstthefireplaceopening•• Ensurethereissufficientoverlaparoundtheperimetertoallow a fume ti
123.5 • Placefivecoalsonthefrontofthefuelbedsotheyreston the front coal effect and lean against the vertical fingers, Diagram 9AR090293
13INSTALLATION INSTRUCTIONSCOMMISSIONING1. COMMISSIONING1.1 • Closeallopenabledoorsandwindowsintheroom • Ignitethestoveandoperateon
14IGNITION FUNCTIONAL CHECK 1PILOT WILL NOT LIGHTEnsure there is no debris around the pilot assembly, (e.g. soot, etc.) which could short the spark,
15SERVICING INSTRUCTIONSFAULT FINDING CHARTSPILOT WILL NOT STAY LIT OR FIRE GOES OUT IN USEEnsure there is no debris around the pilot assembly, e.g. c
163. IGNITION LEAD AND PIEZO Due to the method of manufacture, these components can only be replaced as an integral unit. 3.1 • Turnthegassupply
17AR03203 • Prisethesmallretainingringoutoftheinletandremovethe filter4.2 • Replacewithanewfilterandpushintopositionensuringt
188. PRIMARY AERATION PLATE8.1 • Turnthegassupplyoffattheisolationdevice.8.2 To open the doors: • Slackenthedomednutontheupperdoor
19SERVICE RECORDS1ST SERVICE 2ND SERVICEDate of Service: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Date of Service: ...
2CONTENTSCOVERING THE FOLLOWING MODELSBRUNEL - 8050 - P8050 PAGEAPPLIANCE COMMISIONING CHECKLIST 3 USER INSTRUCTIONS 4 INSTALLATION INSTRUCTIONS
Gazco Limited, Osprey Road, Sowton Industrial Estate, Exeter, Devon, England EX2 7JGTel: (01392) 261999 Fax: (01392) 444148 E-mail: [email protected]
3FLUE CHECK PASS FAIL1. Flue is correct for appliance 2. Flue flow test 3. Spillage test GAS CHECK 1. Gas soundness & let by test2. Standin
4USER INSTRUCTIONS2.3 • Holdinfor5to10secondsandthenrelease The pilot remains lit. If the pilot does not light, repeat the procedure.2AR0
54.2 • Holdinthecontrolknobandrotateanti-clockwiseuntilthe knob is pointing at the ignition symbol ( ★ ) • Applyalightedmatchtothep
6USER INSTRUCTIONSAR090066.4 • Placethreecoalsequallyspacedontherearofthefuelbed so they touch the rear panel, Diagram 7AR090176.5 • Pl
7USER INSTRUCTIONS9. 'RUNNING IN'9.1 The surface coating on your GAZCO stove will ‘burn off’ during the first 24 hours of operation on hig
8INSTALLATION INSTRUCTIONSTECHNICAL SPECIFICATIONCovering the following models Brunel - 8050 - P8050Model Gas Cat.Gas Type Pressure Nox ClassAeration
9INSTALLATION INSTRUCTIONSSITE REQUIREMENTS 1. FLUE AND CHIMNEY REQUIREMENTS1.1 The chimney or flue system must comply with the rules in force, and m